Power System Ripples

 

Power System Ripples

Normal operation of ideal power system is generation follow the load changes. Normal variations of load are small as per start/stop of gadgets by users as per their requirement. Such load variations reflects as frequency change. System operator adjust generation manually or automatic based on frequency drift from normal. This is continuous process at energy management center. Hence grid is operating smoothly with small frequency variations.

But system response is different during sudden major changes of power at any bus due to loss of generation on account of tripping of generator or loss of load on account of tripping of load center or area like partial blackout.

Frequency shifts from current level to new level with slow oscillations of frequency around the trend line. Frequency shift and its trend depends on system bias and system inertia.

Frequency oscillations in power system are analogous to ripples originate and spread around the point of incident while some object fall in standstill water of the pond. This is visual phenomenon for review of oscillations in power system. 

The object falling with speed in the pond enters in the water pulling down water along with leaving water cavity behind. The object moves down the water against up thrust of water buoyancy due to its kinetic energy. Soon after water column shoot up above surface at the point of incidence. The rise and fall of water continue for a while generating ripples around the point. These ripples in water are concentric circles propagating outward from the point of incident because of homogeneous media.

Power system also have similar frequency oscillations at the bus of incidence and generate ripples spreading all around.

Actual grid system may have numbers of buses operating at different voltage levels and network of lines providing multiple interconnections amongst various buses. At each bus power is injected from other stations via few links so also power is drawn from the bus for other stations via other links. Total power imported at the bus and total power exported from the bus are same during normal operation. Net power at any bus is zero and all the stations continue operating in synchronism at grid frequency.

 

 

 

 

 

 

 

 


A station with most simple bus layout is consider to study the phenomenon.

Local bus L is having four lines to stations R, E, T, and U representing different status of power exchanges.

Line to station R represents the lines mostly injecting power to the bus.

Line to station E represents the lines mostly drawing power from the bus.

Line to station T represents the lines mostly floating or injecting or drawing marginal power.

Line to station U represents dumping of local generation to the bus.

Power injected to bus is taken as positive and power drawn from the bus is taken as negative.

PU, PR, PE and PT are power exchange on lines with respective buses.  

So during normal operation of power system PU + PR + PE + PT = 0.

 

 

 

 

 

 

 

 

 

 


Here is vector diagram of the voltages VR, VE VT and VL.

VR is leading VL by angle qRL as power is imported from bus R.

VE legging VL by angle qEL as power is exported to bus E.

VT legging VL by small angle qTL as marginal power is exported to bus T.

 

Now micro step analyses is based on following facts.

Frequency is electrical angular velocity.

Active power flow on link depends on phase angle between the terminal voltages P α δq

(Reactive power flow on link depends on difference between the terminal voltages Q α δV)

Change in power flow on any link is associated with change in power angle. This is feasible only when angular velocity (frequency) at ends are different.

For instance, power angle expands when power flow on line increase. This can occur either due to higher frequency at exporting bus or lower frequency at receiver bus.   

Means frequency of any bus may be different from grid during transit period. This difference of frequencies is very small and short during normal operations as variations in flow itself is smalls. But system behave differently following sudden large unbalance at any bus.    

 Post disturbance has loops of following chain effects.

Occurrence of power unbalance at bus causes drop or rise of local bus frequency.

Concern bus voltage move forward or backward due to rise or drop of frequency.

Power angles between local bus and other end bus changes.

Power exchanges on lines changes with change of power angles.

Net variation of line exchange leads to increase/decrease of surplus/deficit power at the bus.

Change in surplus/deficit power reflects on bus frequency and loop continues. 

 

Cascading effects after loss of generation.

 

 

 

 

 

 

 

 

 


Stage A to B

Consider loss of generation PU at bus L. Frequency starts dropping due to deficit of power at the bus.

Consequently bus voltage VL starts falling back. VS is shifting bus voltage at any time as in diagram.

Phase angles of voltage VR, VE and VT with respect to shifting bus voltage VS are changing.

Leading (positive) power angle qRS is expanding. So power import from bus R is increasing.

Lagging (negative) power angle qES is contracting. So power export to bus E is decreasing.

Lagging (negative) power angle qTS contracts and further change to expanding leading (positive). So power export from to bus T is decreasing and further start increasing import.

Net power exchange on lines will be surplus and increasing. Hence power deficit at the bus is reducing. Therefore rate of fall of frequency at the bus starts decreasing.

After a while surplus power flow on lines matches the loss of generation when frequency drop is arrested because now there is no power shortage at the bus.

Stage B to C

Still bus frequency is low and hence bus voltage continue shifting backward. Power angles continue to change as above. So also power flow on lines continue to change resulting surplus power at the bus. Excess power accelerates bus frequency. Rate of rise of bus frequency is increasing with increasing surplus power.

At a time frequency improves nearly normal level. However bus voltage is at maximum backward. Power angles are at extreme status results in maximum surplus power at the bus. So frequency rise continue and is fastest.

Stage C to D

Frequency continue to rise fastest above normal with maximum surplus power. Now bus voltage starts moving forward due to higher frequency. Power angles qRS, qES and qTS are changing in reverse direction.

Power angle qRS is now contracting. Power import to the bus from bus R is decreasing. Power angle qES is expanding. Power export to bus E is increasing. Power angle qTS starts contracting and power import to the bus from bus T is decreasing. Further angle qTS turn to lagging and expanding. So power import from the bus T changes to export. Net power flow on lines to the bus is reducing.

Surplus power at the bus is reducing. Frequency continue to rise but at reducing rate.

Stage D to E

After a while surplus power flow to bus is nil and frequency rise stops. However frequency is higher than normal and hence bus voltage continue moving forward. Advancing bus voltage causes changes of power angles.

Power angle qRS is now contracting. Power import to the bus from bus R is decreasing. Power angle qES is expanding. Power export from the bus to bus E is increasing. Power angle qTS starts contracting and power import to the bus from bus T is decreasing. Further angle qTS turn to lagging and expanding. So power import from the bus T may change to export.

So net power exchange on lines starts reducing. Resulting deficit of power at the bus cause dropping frequency.

At a time frequency is almost normal level. Power angles are at extreme status resulting net maximum negative power flow on lines. Therefore rate of fall of frequency is maximum.

E onward

Now frequency drops below normal. Bus voltage moves backward. Power angles changes. Net negative power flow on lines is reducing. So also the rate of drop of frequency is decreasing.

Thereafter whole cycle is continuously repeated resulting in frequency oscillations around dropping trend line as in the picture. However frequency oscillations subsides with the time.    

 Spreading of ripples.

Along with frequency oscillations at origin, there was continuous changes in power export / import on directly linked known as first rank stations.  

These changes in power export or import with direct linked stations cause power unbalance at each stations. Higher or lower import or export with the origin bus results in surplus or deficit of power at these stations. So all these stations have frequency oscillations the way as at the origin. Total deficit / surplus at origin was shared by all the neighboring stations as per strength of the stations. Therefore intensity of frequency oscillations at these stations is lower than that at origin and also different at all these station according to their participations.

 

These stations also have their own set of direct linked stations of the grid. These second rank stations participates by change of export import during frequency oscillations at respective first rank stations. So these second rank stations also have frequency oscillations. Of course, oscillations here are very less intense. This way the frequency oscillations spreads around origin successively at next rank stations. But intensity of oscillations is reducing and is insignificant after few steps.  

In case of loss of load, frequency oscillation initiate with rise of frequency and oscillations continue similarly with rising trend of frequency as under. 

In case of tripping of loaded line within the grid, oscillations occurs at both ends. Station exporting power on this line has condition like loss of load whereas station importing power on this line has condition like loss of generation. Of course there is no trend of rise or drop of frequency because there is no net unbalance of power in the grid. Frequency oscillations are around operating grid frequency. Ripples originated from both side meets at intermediate stations. Mostly ripples from both sides are so week and out of phase. But sometimes superimpose to intensify which is threat to security of grid.

Ripples in the pond are uniform all around due to homogeneous media. But spreading of ripples in power system is irregular because of uneven media.

Total shift of frequency on loss of generation or loss of load depends on grid bias and trend of shifting frequency depends on grid inertia. These oscillations are slow in the range of 10 to 20 per minutes depending on physical inertia of buses and electrical inertia of links around origin.

This is basic analyses of frequency oscillations at the point of disturbance in grid and how it spread around in the network. This may be base for analytical evolution of phenomenon. That may further useful to evolve influence of various factors and way for mitigation of risk on this account.